Stop first if
- You smell gasLeave the building now. From outside, call emergency services or the gas utility.
- Flue gas at a drain or dry trap, or a CO alarm soundsVentilate and leave the building. From outside, call emergency services or the gas utility.
- Water is on wiring or controlsKeep clear of it. A qualified person kills power at the disconnect while standing somewhere dry. Otherwise call a licensed electrician.
- The boiler may have run dryKeep clear. Shut it off only if it can be done without risk. Call a licensed boiler technician.
01
Ask on the call
6Homeowner? These are the questions a good technician will ask you. Having the answers ready makes the first visit count.
- Is it hot water or steam?
- Is it the whole system or one zone?
- Is there a code or lockout light?
- Does the relief valve discharge on heat-up?
- Do you hear gurgling or crackling near the pump?
- How often is water added, and is there a fill meter?
02
Bring
6- Pressure gauge
- Surface thermometer
- Air gauge for the expansion tank
- Electrical meter
- Digital manometer
- Flashlight
03
Check on site
6- Name the piping layout. Note where the tank, separator, vent and pump sit.
- Record pressure and supply and return temperature, cold and through heat-up.
- See if relief discharge lines up with heat-up. Note tank type and air charge.
- Listen at the pump inlet.
- Read the fill meter over a known period. Check the relief valve and tank before hunting pipe.
- A licensed boiler tech works on board supply, flow switch, limits and lockout codes.
04
Keep on the record
5- Pressure and temperature log
- Fill meter readings
- Expansion tank charge
- Any code
- Piping photo
General guidance for a qualified person, not a finding about any home. The person on site decides.