Stop first if
- A rollout or manual-reset limit has trippedKeep the furnace off. Call a licensed heating tech. Find the cause before any further reset.
- You smell gasLeave the building now. From outside, call emergency services or the gas utility.
01
Ask on the call
6Homeowner? These are the questions a good technician will ask you. Having the answers ready makes the first visit count.
- How long does it run, and how long is it off?
- Does it happen in heating, cooling or both?
- Does it stop on the thermostat, or on a code?
- Is the thermostat near a supply vent, lamp or sunny window?
- Was there any insulation, window or air sealing work?
- When was the filter changed?
02
Bring
5- Watch or timer
- Handheld thermometer
- Digital manometer
- Electrical meter
- Clean filter
03
Check on site
6- Log run and off times. Note what ends each cycle.
- Read stored codes.
- Check filter and registers. Work out airflow from the maker's table.
- Survey the thermostat location and compare it with a handheld reading.
- On a furnace limit trip, a tech measures temperature rise after warm-up and compares it with the plate.
- If controls and airflow look right, compare a current load calculation with capacity.
04
Keep on the record
5- Cycle log
- Stored codes
- Thermostat location photo
- Temperature rise reading
- Notes on any building envelope work
General guidance for a qualified person, not a finding about any home. The person on site decides.