Skip to content

Lights flicker or dip.

A licensed electrician should take live readings and do any load calculation.

Customers put it like this

  • the lights dim when the AC kicks on
  • my lights keep flickering
  • everything dips when the dryer starts

Stop first if

  • Some lights get brighter while others get dimmer.Keep sensitive gear off if that can be done without risk, and call a licensed electrician now.
  • A burning odor comes with the flicker.Leave the area, call emergency services and make no resets.
01

Ask on the call

5

Homeowner? These are the questions a good technician will ask you. Having the answers ready makes the first visit count.

  1. What starts at the moment the lights dip?
  2. Is it one room, one circuit or the whole house?
  3. Do any lights ever get brighter than normal?
  4. Has any large equipment been added lately?
  5. Is the affected area far from the panel, such as a garage or outbuilding?
02

Bring

5
  • Rated multimeter
  • True-RMS clamp meter
  • Plug-in receptacle tester
  • Flashlight
  • Phone for photos
03

Check on site

6
  1. Note what starts at each dip. A brief dip at motor start points toward normal inrush.
  2. Note whether the dip reaches one room, one circuit or the whole house.
  3. A qualified person reads each leg to neutral through a load swing. Line-to-line alone can hide a neutral problem.
  4. A qualified person reads voltage at the panel and at the load at the same moments.
  5. Note long or undersized runs. Voltage drop grows with current and resistance.
  6. Treat overload signs as a screen only. A load calculation by a licensed electrician answers the question.
04

Keep on the record

4
  • What started at each dip, with the time
  • Voltage at panel and load at the same moments
  • Each leg to neutral during the load swing
  • Size and rough length of the affected run

General guidance for a qualified person, not a finding about any home. The person on site decides.