Stop first if
- It trips at once with everything unplugged or switched off.Stop resetting and leave it off until a licensed electrician checks the circuit.
- There is heat, odor or water at the panel.Stay away from the panel and call a licensed electrician. Call the utility if water is reaching it.
- A larger fuse or breaker has been fitted.Leave the circuit off and have a licensed electrician correct the size and look for the reason.
- Smoke or arcing appears.Leave the area, call emergency services and make no more resets.
01
Ask on the call
6Homeowner? These are the questions a good technician will ask you. Having the answers ready makes the first visit count.
- Does it trip right away, or after something runs for a while?
- What was running or starting when it tripped?
- Does it feed anything buried or outdoors, such as a well or yard light?
- How many times has it been reset so far?
- Has anyone changed a fuse or breaker to a larger size?
- Have you seen rust, water stains, heat marks or a burnt smell at the panel?
02
Bring
6- Clamp meter
- Rated multimeter
- Insulation-resistance tester
- Voltage tester proven on a known source
- Flashlight
- Phone for photos
03
Check on site
6- Record trip timing. A re-trip at once with loads off points toward a fixed wiring or device fault. A delayed trip after a load returns points toward overload.
- Allow one reset only, with loads off, then restore loads one at a time.
- With the door open and cover on, look for rust trails, staining, heat marks and burnt smell.
- Read plug fuse ratings and breaker sizes. Never fit a larger one. A breaker that holds says nothing about a heating joint.
- On buried runs, have a licensed electrician run an insulation test before another reset. Each re-energizing feeds the fault.
- A licensed electrician inspects stab and bus with the panel de-energized before re-seating or replacing a breaker.
04
Keep on the record
5- Trip timing and what was running
- Breaker or fuse size and the load on it
- Photos of rust, staining or heat marks, cover on
- Insulation test results with tester, conditions and sister conductor readings
- Number of resets before arrival
General guidance for a qualified person, not a finding about any home. The person on site decides.